UPS Battery Change

Ferrups

See manual.

  1. Set ups to Inverter mode.
  2. Open front panel and disable circuit breaker. This cuts of battery power to the ups
  3. Remove side panels
  4. Disconnect negative battery terminal from the ups
  5. Disconnect positive battery terminal from the ups
  6. Disconnect batteries from one other
  7. Remove strap and plastic dividers, noting orientation for when reinstalling
  8. Remove old batteries
  9. Install new batteries
  10. Install plastic dividers and strap
  11. Connect side A batteries together with a short cable
  12. Connect side B batteries together with a short cable
  13. Connect side A to side B with long cable
  14. Connect positive terminal to ups
  15. Connect negative terminal to ups
  16. Enable circuit breaker
  17. Set UPS to Auto mode

BestPower